Three Blinds, One Button, Three Different Heights: Travel Time on KNX

A KNX blind actuator cannot see the blind. It works out position from a travel time somebody typed into ETS. How to measure it, keep it honest and test it at handover.

Three Blinds, One Button, Three Different Heights: Travel Time on KNX

You press “half” on the keypad. One blind stops at the sill, the next stops a hand above it, and the third goes nearly all the way down. Same button, same actuator, same command.

Nothing is broken. The actuator was told all three blinds take the same time to travel, and they do not.

The actuator cannot see the blind

A standard 230 V blind motor has a wire for each direction and limit switches inside the tube. It does not report where it is. So the KNX actuator works out position with a clock. It knows how long a full run should take, and it closes the relay for a share of that time.

MDT’s manual for its JAL shutter actuators says it in one line: “The shutter actuator calculates its current positions from the set movement times.” A Siemens KNX promoter, answering a 2014 KNX User Forum question about an older ABB actuator, was blunter: “The actuator will not know the exact position of the blinds.”

So every percentage on the keypad, in the app and in the shading automation is an estimate. It rests on one number somebody typed into ETS.

The default is never your blind

Here is what that number looks like out of the box, in the documents I read for this post:

  • Hager’s application description for the TYAS624C, TYAS624D and TYAS628C lists the complete up and down movement durations at 2 minutes.
  • ABB’s JRA/S manual sets up and down to 60 seconds each.
  • MDT’s JAL manual starts at 45 seconds.
  • Home Assistant’s KNX cover falls back to 25 seconds if you set nothing.

Four different numbers, and none of them came from your blind.

Do the sum on a blind that takes 40 seconds to close but was left on a 60 second setting. Ask for 50% and the actuator runs the motor for 30 seconds. The blind is now three quarters of the way down, and the keypad says 50%.

Now put a 2.4 m sliding door blind and a 1.2 m bedroom blind on the same typed-in time. That is the three heights from the top of this page.

Up and down are two numbers

Hager, ABB and MDT all give separate settings for the up time and the down time. ABB’s manual says the two can differ because of physical and weather effects. A motor lifting the weight of a blind is not doing the same work as one lowering it.

If you time one direction and type it into both fields, the error grows every time the blind stops midway. MDT’s manual says frequent moves that never reach an end stop cause “slight shifts” in the calculated position.

Measure it, or let the actuator measure it

The stopwatch method still works. Do it per blind and per direction, with the real fabric or slats hanging. Start from a hard end stop and time until the motor cuts out. Write both numbers on the commissioning sheet.

Some actuators will measure for you. ABB’s JRA/S does it by current: it detects travel above 300 mA and updates the times on each full run between end positions. The manual attaches two conditions. The drive’s standby current may not exceed 150 mA, and for electronic drives with a permanently connected supply, “automatic travel detection is not possible”.

MDT’s JAL .02 runs a measurement sequence you start from an object or from the buttons on the device, and it keeps correcting afterwards. Their example is winter, when a blind moves a little slower and the stored time gets stretched step by step.

The Hager application description I read does not describe an automatic measurement. On those I would plan for the stopwatch.

Give the blind somewhere to reset

Drift clears whenever the blind hits an end stop. ABB’s actuator updates its stored position every time the blind reaches the top. MDT suggests a reference run “e.g. once a week” for blinds that only ever sit between positions.

In a house, the easy way is to make sure the daily routine includes one full run. The morning scene sends everything to 0%, or the goodnight scene closes fully. A west-facing blind that sits at 60% every afternoon for a month and never goes home will wander.

ABB and MDT also let you add a few percent of extra run time at the end, up to 20%, so the motor is sure to reach its limit switch. MDT notes that the extension does not change the position calculation.

Slats are a second clock

Venetian blinds add a tilt time on top. Hager’s default is 150 ms of relay time per slat step with 12 slat angles. ABB’s is 200 ms per step with 7 steps. MDT says the slat adjustment time must always be set by hand, even when the travel time is measured automatically.

A 2014 KNX User Forum thread shows how small the margin is. Fully lowered venetians were reporting 98% or 99% instead of 100%, and a scene that waited for 100% before tilting the slats never tilted them. A 5% extension did not fix it, and the thread ends without an answer. I include it because a 1% error in a status value was enough to stall a scene.

Test venetian scenes on the real blind. The group monitor will not show you this.

Leave the reversal pause alone

Every one of these actuators forces a pause before the motor changes direction. Hager’s default is 600 ms, adjustable from 300 ms. ABB and MDT default to 500 ms. MDT’s manual carries the warning: “Too short selected reverse pauses can damage the motor!”

Use the figure from the motor maker’s datasheet. Shaving it to make the blinds feel snappier is a bad trade.

After a power cut

MDT’s manual says that unless the actuator is set to save its position, it needs a reference run after programming or after a 230 V failure. A bus failure with mains still present does not need one.

Hager lets you choose what each blind does after an ETS download and when the bus returns: hold, up, down or a specific position.

For a South African house this needs a decision, and I go back and forth on it. After an outage I would rather the blinds made one full run to a known end than trust a percentage from before the lights went out. But nobody wants the bedroom blinds opening at 3am when the power comes back. Settle it per room, with the owner.

Home Assistant keeps its own clock

The Home Assistant KNX cover has its own travelling time setting, with that 25 second default. The integration’s developer explained the logic in a community thread from around the 2022.6 release: Home Assistant estimates the position while the cover moves, and a position status received from the actuator takes precedence.

So link the actuator’s position status to Home Assistant, and set the travel times there too, so the slider moves at the right speed between updates. On the Hager actuators the objects to look for are “Position in % indication” and the two “position reached” bits.

The handover test

Send every blind on one facade to 50% and go and stand outside. They should line up.

Then run each blind through ten short moves without touching an end stop and send it to 50% again. If it has shifted, the up and down times are not right yet.

Tilt the venetians from a scene, on site, and watch them.

Put the measured times in the handover file. Check them again after the first summer, or whenever a fabric is changed for something heavier.

If blinds are part of a house you are planning, it is just a conversation about what the project needs. wayne@knxlogic.co.za | 082 564 3982 | www.knxlogic.co.za


Note on figures: defaults and ranges come from the manuals listed below and differ by device and application version. Confirm them in ETS on the exact device. The 40 second and 2.4 m examples are my own arithmetic, not from a source.

Sources