The quietest KNX failure: a device that just stops talking
A dead KNX device sends nothing, so nothing tells you it is dead. How the cyclic "In operation" telegram works, what it costs the bus, and why it belongs in the spec.

Most KNX faults announce themselves. A light does not come on. A blind will not move. The client tells you within the hour.
The ones that worry me are the faults that make no noise at all. A sensor that has stopped reporting. A gateway with a damaged cable behind a cupboard. A leak sensor that died in March and has been “all clear” ever since. Nothing is wrong on the surface, because a device that has stopped talking sends nothing, and nothing looks exactly like “all is well”.
KNX has a simple answer to this. Most people never switch it on.
What the “In operation” telegram is
Many KNX devices can send a cyclic “I am alive” telegram. It is a one-bit object that repeats on a timer. The receiver does not care what the value is. It cares that it keeps arriving.
I went through manufacturer documentation from two different vendors to see how this is implemented. The ABB DG/S gateway manual describes the “In operation” group object as the way to show the device is present on the bus, and spells out what silence means: the gateway may be faulty, or the KNX cable to the sending device may be interrupted. Its cycle time can be set from 1 second up to 65,535 seconds, which is about 18 hours. An MDT leakage sensor has the same function, with a cycle from 10 minutes to 24 hours.
In the MDT sensor it is off by default. That is the part that matters. If the heartbeat is not enabled in ETS, the device will never tell you it has gone, because it has no way to.
A heartbeat is only half the job
Here is the catch. A device sending “I am alive” achieves nothing unless something is listening for it to stop.
The actuator in the DB does not notice that a sensor has gone quiet. The bus does not raise a flag. A wall panel will happily show the last value it received, hours or days after the source disappeared. Home Assistant is a good example of why this matters: its KNX integration only re-reads a value from the bus after an hour without a telegram by default, per its own documentation. So a dashboard can look settled for a long time after a device has died.
Somebody has to own the question “when did we last hear from this device?” That is a supervision job. It can live in a logic module, in a supervisory system, or in Home Assistant watching the telegram for that address. What it cannot do is live nowhere.
What the heartbeat costs the bus
Less than people expect. I wrote about bus load earlier this month, and the maths is friendly here.
Take 60 devices all sending a heartbeat every 10 minutes. That is 60 telegrams per 600 seconds, which is 0.1 telegram a second. Even at one every minute it is about one telegram a second across the whole installation, and it is spread over lines, not piled on one. A line comfortably carries tens of telegrams a second.
The cost is real if you set a 1 second cycle on everything, so do not. For most devices, five to ten minutes is plenty. Reserve fast cycles for the handful of things where you genuinely need a quick answer, such as a leak or fire input.
Cyclic alarms are the same idea, aimed at the dangerous things
The MDT leak sensor also lets the alarm object itself repeat. The options are on change, cyclic, or both, with a cycle from 10 seconds to 60 minutes and a default of 1 minute. When it is cyclic, the current alarm state is sent again even if nothing changed.
That sounds like a minor detail. It is not. If a single “alarm ON” telegram is lost, or the receiving logic restarted at that moment, a change-only alarm is simply gone. A repeating one gets a second chance every minute. For water, smoke and wind, I want the alarm to keep saying it until somebody deals with it.
After a power cut, the heartbeat tells you who came back
This is the Joburg angle. When power returns after load shedding or a fault, a KNX line does not wake up politely. Dozens of devices start together and all want to send their initial values.
The documentation covers this well. The MDT unit has a startup time parameter from 0 to 240 seconds, default 1 second, used to stagger devices coming up on a busy line. The ABB gateway waits out an inactive period after bus voltage recovery before it sends its cyclic value. Both are there to stop a pile-up on the bus.
For me the interesting part is the other side. After an outage, the heartbeats are your answer to “did everything actually come back?” If every device on a list has checked in within a few minutes, you can sign it off. If three have not, you know where to look, and you know before the client finds the dead blind.
I covered what actuators do on power return in an earlier post. This is the companion question: not what each device does, but how you know it did it.
What a heartbeat does not prove
I want to be straight about the limits.
A heartbeat proves the KNX device is powered, programmed and connected. It does not prove the thing it measures is working. A sensor head can fail while its bus coupler carries on cheerfully reporting “in operation”. Some devices report sensor faults separately and some do not, and the documentation I read for one weather sensor mentions no watchdog or heartbeat function at all. So not every device can do this. Check the application for each model, in ETS, before you promise it to anyone.
I also have not tested any of this on a live Hager or Ekinex project for this post. The behaviour I describe comes from the manuals above. Parameter names and ranges differ between manufacturers, so confirm yours on the actual product.
What I would put in the spec
If you are an architect or designer, this is the short list to hand your integrator:
- A heartbeat enabled on the devices where silence matters: gateways, leak, smoke and gas inputs, weather and wind inputs, and anything feeding a safety function.
- Cyclic sending on safety alarms, so one lost telegram cannot hide a real event.
- A named supervisor that watches for a missing heartbeat and sends a message to a person, not just a red icon on a panel nobody opens.
- A post-power-cut check: after the first outage, confirm every monitored device has reported in.
None of this adds a box to the DB. It is parameters and a supervision rule, written down once.
A KNX system is very good at telling you what happened. The design question is how it tells you that something has stopped happening. If you are planning a project and want that built in from the start, it is just a conversation about what the project needs.
wayne@knxlogic.co.za | 082 564 3982 | www.knxlogic.co.za
Sources
- ABB i-bus KNX DG/S gateway manual, “In operation” group object, page 34: https://www.manualslib.com/manual/1294330/Abb-I-Bus-Knx.html?page=34
- MDT TM SCN 01 leakage sensor manual V10 (cyclic “In operation”, cyclic alarm, startup time): https://www.mdt.fr/fileadmin/user_upload/user_upload/download/MDT_TM_SCN_01_Leakage_Sensor_V10.pdf
- Gewiss KNX weather sensor manual (no watchdog function documented): https://www.gewiss.com/content/dam/gwdam/FILE/ZMN/70161617_EN.pdf
- Home Assistant KNX integration, sync_state behaviour: https://www.home-assistant.io/integrations/knx/